Record · 2013

Building maintenance manual for Jeffrey Epstein's residence, 2013

Confidential 2013 building maintenance schedules for Epstein's residence covering HVAC, heating, steam, fire safety, sewage, generator, and water systems.Machine-written summary

Air Handlers AC 5, 6, 8, 10, 13, 16, 17 AC 5 - 5th floor staff living room. AC 6 - bed room stair AC 8 - 6th floor movie room AC 10- security office AC 13- laundry AC 16- Cellar area pressing/garbage room AC 17- 505 south bed room g. max office Note: Same maintenance as AC1-4; see owner’s manual, section 3, page 4. “The information contained in this document is confidential and is intended only for the use of the authorized recipient. It is the property of Jeffrey Epstein. Unauthorized use, disclosure or copying of this document or any part thereof is strictly prohibited and may be unlawful. © 2013 Jeffrey Epstein - All rights reserved” HOUSE_OVERSIGHT_009537

Hot Water Re-Heat System Bell & Gossett HX1, HX2 – heat exchanges Note: for maintenance check service manual next page; control set points and system from Landis BMS System, building office; Landis steam valve controls steam pressure to heat exchanger, see Siemens SKA Electronic Valve Actuator. Heating System Daily Schedule

  1. Check Supply and return temperature form BMS and unit on SC – level.
  2. Check reheat pump discharge pump pressure 120 psi.
  3. Check water make up PRV. For usage if valve is moist and wet. Make sure it is ni use showing link in system. Weekly Schedule
  4. Check and open heat exchange shell; to blow down valve; condensate- if steam comes out, there is a leak. Monthly Schedule
  5. Clarify water and check corrosion inhibitor levels in system.
  6. Check steam inlets valves for proper operation at BMS and heat exchanger. “The information contained in this document is confidential and is intended only for the use of the authorized recipient. It is the property of Jeffrey Epstein. Unauthorized use, disclosure or copying of this document or any part thereof is strictly prohibited and may be unlawful. © 2013 Jeffrey Epstein - All rights reserved” HOUSE_OVERSIGHT_009538

Steam Reduction System Overall:

  1. Check high pressure steam service.
  2. Check medium pressure steam service.
  3. Check low pressure steam service.
  4. Check high pressure condensate.
  5. Check Pressure reducing valves. Spence
  6. Check Pressure reducing control piolets. Spence
  7. Check Steam traps.
  8. Check Condensate recovery tank.
  9. Check bolted flanges with gaskets.
  10. Check steam heaters/ monthly readings Con ED needs access, will call in advance. Daily Schedule
  11. Checking high (180 pse), medium (45 pse) and low (5-7 pse) pressure readings.
  12. Check steam reduction station for leaks and condensate system.
  13. Check condensate traps and tank for steam passing. Weekly Schedule
  14. Check Con Edison meter readings. NOTE: DO NOT WORK ON HIGH PRESSURE SYSTEM WITHOUT PROPER CON EDISON STREET SHUT DOWN. CON EDISON STEAM EMERGENCY 1- 800-914-9112. “The information contained in this document is confidential and is intended only for the use of the authorized recipient. It is the property of Jeffrey Epstein. Unauthorized use, disclosure or copying of this document or any part thereof is strictly prohibited and may be unlawful. © 2013 Jeffrey Epstein - All rights reserved” HOUSE_OVERSIGHT_009539

Fire Safety System Daily Schedule

  1. Check fire command station 1st bldg office daily. Monthly Schedule
  2. Check main fire pump.
  3. Check sprinkler pump.
  4. Check hall hose cabinet.
  5. Check outside Siamese connection.
  6. Check roof manifold.
  7. Inspect Stand Pipe Sprinkler per NYC law.
  8. Check fire exit.
  9. Fill out stand pipe and sprinkler inspection log for New York Fire Dept. Six Month Schedule
  10. Inspect kitchen ansul system.
  11. Clean smoke alarms throughout the entire residence, Annual Schedule
  12. Clean fire reserve tank.
  13. Check smoke alarms. “The information contained in this document is confidential and is intended only for the use of the authorized recipient. It is the property of Jeffrey Epstein. Unauthorized use, disclosure or copying of this document or any part thereof is strictly prohibited and may be unlawful. © 2013 Jeffrey Epstein - All rights reserved” HOUSE_OVERSIGHT_009540

Sewage Ejector Location: sub cellar, downstairs, left side. Daily Schedule Check daily for proper operation. Weekly Schedule

  1. Check controls weekly, lift floats, see if pumps are out. Monthly schedule
  2. Treat with Citrus solution sump treatment- Clorox bleach. NOTE: IF NOT MAINTAINED PROPERLY, WILL FLOOD! “The information contained in this document is confidential and is intended only for the use of the authorized recipient. It is the property of Jeffrey Epstein. Unauthorized use, disclosure or copying of this document or any part thereof is strictly prohibited and may be unlawful. © 2013 Jeffrey Epstein - All rights reserved” HOUSE_OVERSIGHT_009541

Emergency Generator

  1. Location above 6th floor fan room.
  2. Check control panel.
  3. Check NICAD battery rack system. Weekly Schedule
  4. Check operation.
  5. Check battery bank. When Needed
  6. Check oil every 200 hours. Note: Refer to white electrical manual for complete preventative maintenance in bldg. office. “The information contained in this document is confidential and is intended only for the use of the authorized recipient. It is the property of Jeffrey Epstein. Unauthorized use, disclosure or copying of this document or any part thereof is strictly prohibited and may be unlawful. © 2013 Jeffrey Epstein - All rights reserved” HOUSE_OVERSIGHT_009542

Domestic Hot and Cold Water System Overall:

  1. Check control pressure pump.
  2. Check hot water heater.
  3. Check electrical back up hot water heater.
  4. Check bathroom, high medium, low pressure piping and shut off valves with pressure gauges. Domestic Hot Water System
  5. Check Patterson Kelly hot water heaters supply temperature.
  6. Check Bell & Gossett recirculation pumps.
  7. Check steam control valve to heater.
  8. Check pressure relief valve for water leaks. As Needed
  9. Add oil to Bell and Gossett pumps (every 2 to 3 months). Domestic Cold Water (Constant Pressure) System
  10. Check pump operation.
  11. Check system pressure.
  12. Check area leaks. “The information contained in this document is confidential and is intended only for the use of the authorized recipient. It is the property of Jeffrey Epstein. Unauthorized use, disclosure or copying of this document or any part thereof is strictly prohibited and may be unlawful. © 2013 Jeffrey Epstein - All rights reserved” HOUSE_OVERSIGHT_009543

Building maintenance manual for Jeffrey Epstein's residence, 2013

Other records

Confidential 2013 building maintenance schedules for Epstein's residence covering HVAC, heating, steam, fire safety, sewage, generator, and water systems.

House Oversight: Estate Documents (Oct 17) · 2013

Air Handlers AC 5, 6, 8, 10, 13, 16, 17 AC 5 - 5th floor staff living room. AC 6 - bed room stair AC 8 - 6th floor movie room AC 10- security office AC 13- laundry AC 16- Cellar area pressing/garbage room AC 17- 505 south bed room g. max office Note: Same maintenance as AC1-4; see owner's manual, section 3, page 4. "The information contained in this document is confidential and is intended only for the use of the authorized recipient. It is the property of Jeffrey Epstein. Unauthorized use, disclosure or copying of this document or any part thereof is strictly prohibited and may be unlawful. ©…